產(chǎn)品概述Product Brief
The static reactive power generator SVG adopts a power-electronic device (IGBT) that can be turned off to form a self-commutated bridge circuit, connected in parallel to the power grid through a reactor, and appropriately adjusts the amplitude and phase of the output voltage of the AC side of the bridge circuit, or directly Control its AC side current. Quickly absorb or emit the required reactive power to achieve the purpose of quickly and dynamically adjusting reactive power. As an active compensation device, it can not only track the inrush current of the impact load, but also track and compensate the harmonic current.
靜止無功發(fā)生器SVG采用可關(guān)斷電力電子器件(IGBT)組成自換相橋式電路,經(jīng)過電抗器并聯(lián)在電網(wǎng)上,適當(dāng)?shù)卣{(diào)節(jié)橋式電路交流側(cè)輸出電壓的幅值和相位,或者直接控制其交流側(cè)電流。迅速吸收或者發(fā)出所需的無功功率,實(shí)現(xiàn)快速動(dòng)態(tài)調(diào)節(jié)無功的目的。作為有源型補(bǔ)償裝置,不僅可以跟蹤沖擊型負(fù)載的沖擊電流,而且可以對(duì)諧波電流也進(jìn)行跟蹤補(bǔ)償。
混合補(bǔ)償SVGC示意圖Schematic diagram of mixed compensation SVGC
注Note:
無源單組的補(bǔ)償容量一定要小于有源的補(bǔ)償容量,才可達(dá)到細(xì)補(bǔ)的要求。
The compensation capacity of the passive single group must be smaller than the active compensation capacity to meet the requirements of fine compensation.
技術(shù)參數(shù)表Technical Data Sheet
過載能力 | Overload capacity | 120%,1min,110%長期運(yùn)行,120%短期運(yùn)行(0.5h-1h) |
冷卻方式 | cooling method | 強(qiáng)迫風(fēng)冷 |
通訊接口 | Communication Interface | RS232/Modbus |
噪音水平 | Noise level | <65dB@1m |
無功補(bǔ)償能力 | Reactive power compensation ability | -1~1 |
功能設(shè)置 | Function settings | SVG、TSVG |
海拔高度 | Altitude | 2000米/最高4000米,1%/100米降容 |
響應(yīng)時(shí)間 | Response time | 暫態(tài)響應(yīng)時(shí)間300us,全響應(yīng)時(shí)間10ms |
電流互感器 | Current Transformer | 300:5到50000:5(可靈活設(shè)置)開環(huán)連接 |
電路拓?fù)?/span> | Circuit topology | 三電平 |
通訊接口 | Communication Interface | RS485,網(wǎng)口 |
通訊協(xié)議 | Protocol | 電總協(xié)議,Modbus協(xié)議、TCP/IP、DTU/FTU |
快速響應(yīng)時(shí)間 | Fast response time | <50μs |
全響應(yīng)時(shí)間 | Full response time | <5ms |
開關(guān)頻率 | On-off level | 30kHz |
保護(hù)功能 | Protective function | 過壓保護(hù)、欠壓保護(hù)、短路保護(hù)、過補(bǔ)償保護(hù) |
故障報(bào)警 | error alarm | 500條 |
監(jiān)控 | monitor | 獨(dú)立/集中監(jiān)控 |
顯示屏 | Display | 彩色觸摸屏 |
安裝方式 | Installation method | 機(jī)架式/壁掛式 |
防護(hù)等級(jí) | Protection level | IP20可定制 |
電網(wǎng)頻率 | Grid frequency | 50Hz/60Hz |
遵循標(biāo)準(zhǔn) | Follow the standard | IEEE519\IEC 61000-3-6,ER G5/4 |
資質(zhì)認(rèn)證 | Certification | CQC認(rèn)可實(shí)驗(yàn)室型式試驗(yàn)報(bào)告 |
常用規(guī)格&產(chǎn)品尺寸Common specifications & product size
各型號(hào)具體外形尺寸定義見下圖,詳細(xì)尺寸見下表。
See the following figure for the definition of specific external dimensions of each model, and the following table for detailed dimensions.
模塊外形尺寸定義
Order code 訂購代碼 | Module capacity 模塊容量/kvar | System voltage 系統(tǒng)電壓/V | W 寬/mm | D 深/mm | H 高/mm | Weight 重量/kg |
IVD-SVG35 | 35 | 208~690 | 375 | 550 | 170 | 20 |
IVD-SVG50 | 50 | 208~690 | 500 | 550 | 200 | 35 |
IVD-SVG75 | 75 | 208~690 | 500 | 580 | 240 | 40 |
IVD-SVG100 | 100 | 208~690 | 500 | 650 | 270 | 50 |
IVD-SVG150 | 150 | 208~690 | 500 | 650 | 270 | 60 |
★以上僅列出常用型號(hào),其他規(guī)格請(qǐng)洽本公司。
無功補(bǔ)償容量選型:一般按照變壓器容量的30%進(jìn)行選型,例如變壓器容量為1250KVA,則需要配備375Kvar的無功補(bǔ)償,混補(bǔ)模式可配備75Kvar有源+300Kvar的無源(注:無源每組的補(bǔ)償容量一定要小于有源的補(bǔ)償容量,才可達(dá)到細(xì)補(bǔ)的要求。)
Reactive compensation capacity selection: Generally, the selection is based on 30% of the transformer capacity. For example, the transformer capacity is 1250KVA, then 375Kvar reactive power compensation is required, and the mixed compensation mode can be equipped with 75Kvar active + 300Kvar passive (Note: None The compensation capacity of each source group must be smaller than the active compensation capacity to meet the requirements of fine compensation.)